Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/29/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* 1. NEED LETTER FROM CONTRACTOR ACCEPTING RESPONSIBILITY FOR ALTERATION OF DESIGN THAT MAY VOID WARRANTEE OR LISTING FROM MANUFACTURER THIS IS PERTAINING TO DEAD FRONT MODIFICATION BY THIS CONTRACTOR, PIROR TO FINAL APPROVAL. |
| 11/16/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) SUPPORT #4 BARE FOR GAS & WATER BOND (HANGING DOWN ROOF OVER HANG.) 2.) PROPERLY INSTALL 1 1/2" CONDUIT AT TOP OF PANEL, NEEDS TO BE MOVED BACK AND SALED PROPERLY. DEAD FRONT OF SERVICE PANEL DOES NOT REST PROPERLY CIRCUIT BREAKERS PER MANUFACTURER'S DESIGN. 110-3 N.E.C. |