Permit: T01EL02705

Parcel: 127121820


Addresses:

5713 E 7TH ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/29/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245* 1. NEED LETTER FROM CONTRACTOR ACCEPTING RESPONSIBILITY FOR ALTERATION OF DESIGN THAT MAY VOID WARRANTEE OR LISTING FROM MANUFACTURER THIS IS PERTAINING TO DEAD FRONT MODIFICATION BY THIS CONTRACTOR, PIROR TO FINAL APPROVAL.
11/16/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) SUPPORT #4 BARE FOR GAS & WATER BOND (HANGING DOWN ROOF OVER HANG.) 2.) PROPERLY INSTALL 1 1/2" CONDUIT AT TOP OF PANEL, NEEDS TO BE MOVED BACK AND SALED PROPERLY. DEAD FRONT OF SERVICE PANEL DOES NOT REST PROPERLY CIRCUIT BREAKERS PER MANUFACTURER'S DESIGN. 110-3 N.E.C.