Permit: T01EL02702

Parcel: 123122100


Addresses:

1037 E EDISON ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01EL02702

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/21/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000* OK FOR FINAL
11/19/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) DOUBLE LUGGING AT 1ST DISCONNECT TWO STRANDED WIRES UNDER 1 SCREW AND AT NEUTRAL ON 2ND DISCONNECT. 2.) NEUTRAL TO BE WHITE ENTIRE LENGTH. 3.) NEED PERMANENT METAL ADDRESS LABELS. 4.) ROMEX FEED TO BACK BUILDING IS AN UNSAFE CONDITION WIRE DETERIORATING AND CLEARENCE TO GROUND 5.) LABEL BREAKERS 6.) LOOSE FITTINGS.