Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/21/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* OK FOR FINAL |
| 11/19/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) DOUBLE LUGGING AT 1ST DISCONNECT TWO STRANDED WIRES UNDER 1 SCREW AND AT NEUTRAL ON 2ND DISCONNECT. 2.) NEUTRAL TO BE WHITE ENTIRE LENGTH. 3.) NEED PERMANENT METAL ADDRESS LABELS. 4.) ROMEX FEED TO BACK BUILDING IS AN UNSAFE CONDITION WIRE DETERIORATING AND CLEARENCE TO GROUND 5.) LABEL BREAKERS 6.) LOOSE FITTINGS. |