| 11/16/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 11/08/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) INSTALL 2 GROUND RODS 6' APART. 2.) BOND WATER & GAS LINES. |
| 11/06/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1.) NEED SEALING LOCKNUT AT TOP ENTRY INTO PANEL. 2.) STRAP 1/2" EMT PER CODE. 3.) NEED PERMANET METAL ADDRESS TAG PER CITY AMMEND. 4.) REFASTEN BOTTOM OF PANEL. |