Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/15/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL HOLD POWER UNTILL TRAILER/MOBILE HOME IS CLEARED. |
| 11/13/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) USE PVC CEMENT LISTED FOR ELECTRICAL USE. 2.)NEED UP GRADE PERMITS FOR WORK DONE #3 & #2. 3.) BOND ENCLOUSER 4.) NEED GROUNDING EQUIPMENT CONDUCTOR 5.) CLEAN SURFACE UNDER GROUNDBAR 6.) CAN NOT USE SHEET METAL SCREWS TO SECURE GROUND BAR 7.) NEED BONDING DEVICE ON SERVICE NIPPLES IN GUTTER. 8.) USE CORRECT DEVICE AT MIDWEST BOX , DEVICE IS 125V AND WIRED 220V. DEVICE ALSO BROKEN. |
| 11/05/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 11/04/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |