Permit: T01EL02667

Parcel: 127081730


Addresses:

5417 E 10TH ST

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
11/26/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*DENIED NOTES NO COMPLIANCE WITH ITEM #3 1" CONDUIT.
11/09/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*NOTES 1.) MUST HAVE 8' MIN EACH GROUND ROD IN EARTH. PER ART 250 N.E.C. 2.) INSTALL SEALING LOCKNUTS FOR TERMINATIONS ON TOP/SIDE OF SERVICE. 3.)INSTALL CONNECTOR WITH BUSHED ENDS WHERE CABLE EXIST CONDUIT 300-15 C NEC.
11/02/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*