Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/26/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*DENIED NOTES NO COMPLIANCE WITH ITEM #3 1" CONDUIT. |
| 11/09/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) MUST HAVE 8' MIN EACH GROUND ROD IN EARTH. PER ART 250 N.E.C. 2.) INSTALL SEALING LOCKNUTS FOR TERMINATIONS ON TOP/SIDE OF SERVICE. 3.)INSTALL CONNECTOR WITH BUSHED ENDS WHERE CABLE EXIST CONDUIT 300-15 C NEC. |
| 11/02/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245* |