Permit: T01EL02666

Parcel: 13810018B

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
11/29/2001 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*REPAIR ADJUSTMENT AND CODE VIOLATIONS ABATED. OK TO CLEAR TO TEP FOR RECONNECTION POWER.
11/27/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0920*LOCKED.
11/05/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*1.) PERMANENTLY COVER HOLE ABOVE SERVICE BOX SUBPANEL FEEDER AT BREAKER NEEDS TO BE TAPED. 2.) SUB PANEL FEEDER AT BREAKER NEEDS TO BE TAPED. 3.) NEED TO HAVE CONDUIT TO SHED COMPLETELY REMOVED MUST SEE INTERIOR OF STORAGE FOR ELECTRICAL 4.) 30 AMP BREAKER IS DOUBLE LUGGED. 5.) PLEASE MAKE ADJUSTMENT TO ALL WROUGHT IRON WINDOW GUARD FOR EASY OPEING 6.) PLEASE INSTALL A BATTERY STYLE SMOKE DETECTOR IN CENTER OF LONG HALLWAY RECALL INSPECTION.
11/02/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*1.) ALL SERVICE SECOND 60A BREAKER HAS WIRING WITH CROCKED INSULATION WHICH IS WITH IN 1/4" OF NEUTRAL, THIS IS A HAZARDOUS CITUATION WHICH NEEDS TO BE CORRECTED BY OWNER. 2.) REMOVE DOUBLE LUGGING AT 30 A BREAKER. 3.) ONE WIRE OF BREAKER, THRU SHOULD BE 20AMP BREAKERS NOT 30 A IN PANEL. 4.) PROVIDE SCREW FOR PANEL COVER. NO ACCESS TO UNIT TO BE RECALLED FOR MONDAY 11/5/01