Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL02650
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
11/27/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) ENCLOUSER BONDS TO BE TO ENCLOUSER NOT FLAT WASERS 2.) USE APPROVED FITTING TO SLB CHASE NIPPLE NOT APPROVED. 3.) NEED LOCK NUTS ON NIPPLE. 4.) UFER COVERD WITHOUT INSPECTION. 5.) LABEL BREAKER | |
11/04/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) NEED BOND BUSHING IN METER SOCKED ON NIPPLE 250-94. 2.) EXPOSED CONDUCTOR AT DISCONNECT AND POLE. 3.) PROTECT CONDUCTORS 4.) BOND BOTH ENCLOSURES 5.) BOND GROUNDING ELECTRODE TO GROUNDED CONDUCTOR 6.) UFER COVERED WITHOUT INSPECTION. |