Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL02644
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/11/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
01/18/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) PEDISTAL REQUIRES 3' OF CLEARANCE.2.) CONDUIT UNDER MH HAS TO BE PROPERLY SUPPORTED FROM THE FRAME NOT SEWER LINE OR OTHER PIPING. 3.) THE NYLON TYRAPS NOT ALLOWED FOR THIS TYPE OF SUPPORT AFTER TIME THEY WILL BREAK SUPPORT EVERY 6' FEET, AND AT ENDS. | |
12/06/2001 | ELECTRIC - FINAL | Denied | 1.) AT PEDISTRAL 1 1/2" PVC ABOVE GROUND TO BE SCH 80 2.) 1 1/2 PVC CONNECTOR HAS TO RUN INTO BLACK OF PEDISTAL AND HAVE A LOCK NUT, ALSO PIPE TO BE STRAIGHT UP AND DOWN. 3.) PIPE UNDER TRAILER PULLED APART, NOT GLUED ALSO NOT SUPPORTED THUR OUT UNDERSIDE. 4.) MAIN BRAKER IN PANEL HAS TO HAVE TIE DOWN BECAUSE ITS BACK FED. | |
12/06/2001 | ELECTRIC - FINAL | Denied | CANNOT LOCATE WILL GET NUMBER @ OFFICE TO GET DIRECTION. I'VE BEEN REQUEST THAT ADDRESS BE POSTED PER COUNTY LAW. | |
11/30/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*MUST PERMANENLTY PAST ADDRESS IN A CONSPICUOUS PLACE 3' LETTER/NUMBER. | |
11/07/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*11:30 CALLED #ABOVE NO ANSWER #1. THE GROUND RODS HAVE TO BE AT LEAST 6' APART. 2.) THE GROUND WIRE FROM THE GROUND RODS HAS TO BE TIED TO THE NEUTRAL BAR DENIED. | |
11/05/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920$DENIED NO ADDRESS POSTED ANY WHERE CANNOT LOCATE. MESSAGE TO CALLER WIL BE IVR. |