Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL02618
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OWNER RUBEN RENDON TO INSTALL ALL SWITCHES AND RECEPTACELS COVERS IN PLACE PRIOR TO ENGERGIZING. | |
| 11/07/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) PLAN ASKING FOR A MAIN 100AMP CB IN PANEL. 2.) SERVICE DOES NOT HAVE A VIABLE GROUNDING SYSTEM IT NEEDS A WATER AND GAS BOND WITH 2 GROUND RODS 6' APART. 3.) INTERMEDIATE NEVER INSPECTED. #1 OK WITH 100 AMP MAIN CB AT PANEL NEED TO INSTALL #2 AND CALL BACK. |