Permit: T01EL02588

Parcel: 132160250


Addresses:

1501 E BERNARD DR


Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Permit Number - T01EL02588

Inspection Description - ELECTRIC - CONSTRUCTION POWER

Inspection Status - Approved

Date Description Inspector Results Comments
11/21/2001 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection 0000*PLEASE CLEAR FINAL NEW SERVICE ON POLE.
11/13/2001 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection 0920*
11/07/2001 ELECTRIC - CONSTRUCTION POWER Denied IVRS - Inspection 0999*DENIED. 1.) SERVICE IS TOO LOW AT WEATHERHEAD THE POINT OF ATTACHMENT WHERE TEP WILL TIE MUST BE AT LEAST 10' 2.) 4 X 6' BEAM CANNOT BE TIED TO FENCE MUST BE BURIED AND SUPPORTED ON ITS OWN 3.) THIS SERVICE IS TOO OLD TO BE USED DOES NOT HAVE PROPER DEAD FRONT COVER. 4.) ALL NEW SERVICES HAVE TO HAVE A PERMANENT ADDRESS LABEL MARKER NOT ACCEPTED.5.) ALL RISERS TO HAVE TWO SUPPORTS. 6.) BACK BOARD ON WHICH SERVICE MOUNTED MUST BE WEATHERPROOF OR PAINTED. 7.) CONDUCTORS COMING OUT OF WEATHER HEAD MUST BE AT LEAST 2' LONG.