| 11/21/2001 |
ELECTRIC - CONSTRUCTION POWER |
|
Approved |
IVRS - Inspection 0000*PLEASE CLEAR FINAL NEW SERVICE ON POLE. |
| 11/13/2001 |
ELECTRIC - CONSTRUCTION POWER |
|
Denied |
IVRS - Inspection 0920* |
| 11/07/2001 |
ELECTRIC - CONSTRUCTION POWER |
|
Denied |
IVRS - Inspection 0999*DENIED. 1.) SERVICE IS TOO LOW AT WEATHERHEAD THE POINT OF ATTACHMENT WHERE TEP WILL TIE MUST BE AT LEAST 10' 2.) 4 X 6' BEAM CANNOT BE TIED TO FENCE MUST BE BURIED AND SUPPORTED ON ITS OWN 3.) THIS SERVICE IS TOO OLD TO BE USED DOES NOT HAVE PROPER DEAD FRONT COVER. 4.) ALL NEW SERVICES HAVE TO HAVE A PERMANENT ADDRESS LABEL MARKER NOT ACCEPTED.5.) ALL RISERS TO HAVE TWO SUPPORTS. 6.) BACK BOARD ON WHICH SERVICE MOUNTED MUST BE WEATHERPROOF OR PAINTED. 7.) CONDUCTORS COMING OUT OF WEATHER HEAD MUST BE AT LEAST 2' LONG. |