Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/16/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
|
| 11/14/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*3 EXISTING APARTMENT (THERE IS ALREADY 3 GAS METER FOR THE UNITE) ON ONE ELECTRIC METER WILL NOW HAVE THEIR OWN METER. NEED TO REVISE PERMIT TO REFLECT THE ADDITIONAL 2 METER LOOP AND FOR OFFICE TO VERIFY APARTMENT. |
| 10/31/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*1.) INSTALL PERMANENT ADDRESS LABELS WITH UNIT #'S. SCREWED OR RIVITED TO ENCLOUSRE 230-70 NEC. #9287 CITY ORDIN. ON RISER, GUTTER. 250-94 NEC. 3.) ONLY 2 WIRES ALLOWED PER TAP ON SPLIT BOLTS 110-3 NEC. |