Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/26/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*SERVICE IS OK NEED TO SEE PANEL TERMINATION INSIDE TO APPROVE |
| 10/19/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*NEED TO INSTALL GROUNDING BUSHING AT BOTH SIDES OF OFFSET NIPPLE. 99 NEC 250-94 DOES NOT ALLOW A STANDARD LOCK NUT ON AN FITTING TO BE A GROUNDING MEANS WHERE UPPROTECTED CONDUITORS RUN THUR ALSO NEED TO SEE INSIDE CONNECTION. |