Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL02540

Parcel: 111060080

Inspection Status: Denied

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
11/27/2001 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0245*NOTES 1.) NO COMPLIANCE WITH ITEM #4,5,7,9,10. 2.) PROVIDE CITY APPROVED L-LINE DIAGRAM AND LOAD CALC'S REFELCTING ALL WORK DONE BY THIS CONTR. 3.) E-CALL INSPECTION WHEN PROPER PATPER WORK IS POSTED ON JOB SITE AND CORRECTIONS ARE DONE.
10/24/2001 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0245*NOTES 1.) LABEL ALL DISCONNECTS, LOAD CENTERS PANELS, TO REFLECT UNITS SERVED MUST BE PERMANENT, 230-70 N.E.C. # 9287 CITY ORDIN. 2.) INSTALL BONDING LOCKNUTS OR BOND BUSHINGS IN GUTTER ABOVE SERVICE PER 250-94 NEC. 3.) SCRAPE OFF ENAMEL UNDER GROUND LUGS IN ENCLOSURES TO ENSURE CONTINUETY. 250-96 NEC. 4.) GROUNDING ELECTRODE SYSTEM TO BE INSTALLED AT SEPERATE BLD'S PER 250-32N.E.C. 5.) J-BOX AT BASE OF UNITS 4 & 5 WHERE FEEDERS EMERG. FROM GROUND IS UNSAFE, EXPOSED WIRING NEEDS TO BE RE-INSTALLED PROPERLY. 6.) COLOR CODE NEUTRALS AND GROUNDS PROPERLY IN GUTTERS. 7.) PERMIT REQUIRED FOR ADDITIONAL WORK DONE AT UNITS 8.) IMPROPER WIRING METHODS FOR WATER HEATER PULL-OUTS. 9.) BOND WATER AND GAS PIPING EACH UNIT. 250-104 NEC. 10.) SIZE GROUNDING ELECTRODE COND. PER 250-66.