Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/30/2002 |
ELECTRIC - TEMPORARY SERVICE |
|
Approved |
|
| 04/22/2002 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0215*STATE SEAL ON PIPE TO COACH NOT PRESENT CALL FOR STATE INSPECTION. |
| 04/09/2002 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0999*HORIZONAL ROD MUST BE 2 1/2 DEEP MOVE TOWARDS NORTH APPROVED FOR CABLE DROP ONLY. LAST INSPECTION WILL CALL POWER. |
| 03/27/2002 |
ELECTRIC - TEMPORARY SERVICE |
|
Denied |
IVRS - Inspection 0215*THE PEDESTAL IS READY TO RECEIVE PRIMARY CABLE AND POWER FROM TEP, HOWEVER, WE CITY OF TUCSON INSPECTORS, CANNOT APPROVE THE ENERGIZING OF THE COACH. |