Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T01EL02521
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/30/2002 | ELECTRIC - TEMPORARY SERVICE | Approved | ||
| 04/22/2002 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection 0215*STATE SEAL ON PIPE TO COACH NOT PRESENT CALL FOR STATE INSPECTION. | |
| 04/09/2002 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection 0999*HORIZONAL ROD MUST BE 2 1/2 DEEP MOVE TOWARDS NORTH APPROVED FOR CABLE DROP ONLY. LAST INSPECTION WILL CALL POWER. | |
| 03/27/2002 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection 0215*THE PEDESTAL IS READY TO RECEIVE PRIMARY CABLE AND POWER FROM TEP, HOWEVER, WE CITY OF TUCSON INSPECTORS, CANNOT APPROVE THE ENERGIZING OF THE COACH. | |
| 03/25/2002 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection 0999*1.) THE 2 GROUND RODS BEING USED NEED TO BE 6' APART. 2.) TEMPORARY SUPPORT PEDISTAL SO ITS LEVEL UP & DOWN. 3.) CANNOT RELEASE ANY POWER PERMANENT OR TEMPORARY UNTIL STATE OF ARIZONA STICKER IS ON SERVICE. |