Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL02517

Parcel: 10612144B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/19/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/17/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*1.) REMOVE GREEN GOUND WIRES FROM THE TWO LUG STRIP AT BOTTOM OF PANEL 2.) INSTALL A #4 BARE OR GREEN CONDUCTOR FROM THIS STRIP TO THE NEUTRAL BUSS ABOVE IT. 3.) ATTACH THE GREEN GROUND FROM THE GFCI OUTLET TO THIS SAME NEUTRAL STRIP. 4.) INSTALL A #6 GREEN CONDUCTOR FROM THE NEUTRAL STRIP TO THE GROUND TERMINAL OF THE 50 AMP RECEPTACLE.