Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T01EL02496
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/25/2002 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection 0000*AS PER CONVERSATION WITH BOB HALL (MECH ELECT) MAIN 200 A DISCONNECT FOR EXISTING EQUIPMENT NOT TO BE ENERGIZED UNTIL NEUTRAL BLOCK INSPECTED THIS CLEARANCE IS FOR A PARTIAL CHANGE OVER CALL FOR FINAL WHEN CHANGED OVER. FU. 2/25/02 | |
01/18/2002 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection 0210*NOTES: 1.) THE NEUTRAL CONDUCTORS AT THE FIRST SERVICE SWITCH ARE LOOSE TERMINATE & TIGHTEN. 2.) THE GROUNDING CONDUCTOR IS SUPPORTD TO RUN UNBROKEN AND UNSPLICED TO THE NEUTRAL BAR OF THE FIRST SERVICE SWITCH. REMOVE FROM THE 3 COMPARTMENT LUG & BUTT SPLICE WITH CRIMP SLEEVE. 3.) A BONDING SCREW SHOULD BOND THE NEUTRAL TO THE 1ST SWITCH ENCLOSURE. CORRECT & RECALL. | |
01/14/2002 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection 0245*1.) THE UFER MUST BE TERMINATED ON THE NEUTRAL BAR OF EACH MAIN SWITCH. AND THE BONDING SCREW INSTALLED OT BOND THE EQUIPMENT CANS. 2.) THE LINE SIDE CABLES ARE NOT LANDED. 3.) THE 2ND MAIN SWITCH IS NOT WIRED IN. |