Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL02478
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/11/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*APPROVED OK TO CLEAR RECONNECT WILL NOTIFY TEP. | |
10/10/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1. SERVICE REQUIRES IT'S OWN GROUNDING ELECTRODE SYSTEM 2. A BUSYING IS REQUIRED FOR THE ENTRY NIPPLE 3. NEED GROUNDING BUSHING AT PANEL BOARD ENTRY. 4. ISO GROUNDS & NEUTRALS 5. WILL NEED TO SEE FINAL APPROVAL ON * NEW ROOF/TRUSSES & PLUMBING 6. PLEASE CALL 791-5550 EX. 136 & LEAVE INFORMATION OF TYPE OF VSEAGE FOR THIS SPACE. * NOTE NEW ROOF/TRUSSES. |