Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/26/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP. |
| 10/23/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) INSTALL PERMANENT ADDRESS ON SERVICE. 2.) KO IS BREAKING OUT ON SIDE OF ENCLOSURE FOR 1 1/4" CONDUIT. 3.) SUPPORT 1 1/4" CONDUIT 4.) DO NOT COMBINE NEUTRALS AND GROUNDS IN SUB-PANEL. INSTALL GROUND BAR FOR EQUIPMENT GROUND. |
| 10/16/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*NO FURTHER INSPECTIONS UNTIL LICENSED ELECTRICAL CONTRACTOR IS PERFORMNG WORK. PLEASE VERIFY CONTRACTOR WITH OFFICE. |
| 10/08/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) NEED PERMANENT METAL ADDRESS LABEL 2.) NEED 2 GROUND RODS 3.) IDENTIFY NEUTRAL CONDUCTOR AT WEATHER HEAD AND POINT OF TERMINATION 4.) STRAP GROUNDING ELECTRODE CONDUCTOR 5.) NEED TO SEE CONNECTIONS TO STRUCTURE 6.) VERIFY LICENSED ELECTRICAL CONTRACTOR 7.) NEED 1/4" MININUM HARDWARE TO SUPPORT PANEL & BOARD 8.) VERIFY PERMIT FOR A/C INSTALLATION. |