Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/16/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP. |
| 11/13/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) PROVIDE SLEEVE TO COVER CABLING GOING INTO ATTIC THRU SIDING 2.) USE 1/4" MIN BOLTS TO SUPPORT RISER CONDUIT 3.) EXPOSE SECOND GROUND ROD. 4.) NEED TO VERIFY WATER AND GAS BOND. 5.) INSTALL PERMANENT ADDRESS LABEL ON SERVICE. |