Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 12/06/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*UNIT #5 OK OK TO CLEAR UNITS #5. |
| 11/23/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) NO COMPLIANCE WITH INSPECTION WRITE UP FROM 11-21-01 PER RAY M. 2.) A RE-INSPECTION FEE WILL BE ASSESED NEXT INSPECTION IF NO PROGRESS. |
| 11/21/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1.) BURY THE COPPER TO WATER & GAS LINE AT 5 2.) HOW IS #3 ABOVE ACCOPLISHED BUILDING 6 & HAVING ITS OWN GROUNDING SYSTEM TIED TO PANELS 3.) NO LADDER UNABLE TO VERIFY 5-6-7. WILL RETURN FRI WITH A LADDER OR PLEASE HAVE ONE ON SITE TO CHECK ROOF. |
| 10/24/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) GROUND RODS NEED TO BE FLUSH WITH GRADE LEVEL. (TRIP HAZARD). 250-52 N.E.C. 2.) BOND WATER AND GAS PIPING EACH UNIT. 250-104 N.E.C.3.) SEPERATE BLD. OR DUPLEX FOR UNITS 6 AND 7 TO HAVE GROUNDING ELECTRODE. SYSTEM INSTALLED PER. 250-32 N.E.C. SYSTEM INSTALLED PER. 4.) #2 ALUM SE CABLE NOT RATED FOR 100 AMPS 310-16 N.E.C.5.) GROUND TAPS ON SPLIT BOLTS IN J-BOXES NOT APPROVED, SPLIT BOLTS NOT LISTED FOR MULTI TAPS. ALSO DO NOT MIX COPPER AND ALUMINUM TOGETHER 110-3 N.E.C PER UL.LISTING. 6.) INSULATION TAPING ON SPLIT BOLTS MUST BE EQUIVALENT TO INSULATION OF CONDUCTOR BEING SPLICE 110-3 N.E.C. 110-7 , 110-14-B 7.) SUPPORT J-BOXES PROPERLY 110-12 N.E.C. |
| 10/02/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000*OK CABLE DROP TO ALLOW CONTR. TO BACKFILL TRENCH, NO POWER AT THIS TIME. |