Permit: T01EL02422

Parcel: 113082930

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/23/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OKTO CLEAR.
10/19/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*COULD NOT ENTER. DOG IN YARD PLEASE TIE UP OR PUT INSIDE BEFORE I GO IN YARD. PLEASE RECALL AND LEAVE ME A MESSAGE.
10/02/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) IDENTIFY NEUTRAL CONDUCTOR CLOSER TO WEATHER HEAD 2.) NEED BONDING DEVICE ON OFFSET NIPPLE IN SERVICE GUTTER 250-94. 3.) BOND GUTTER ENCLOUSER 250-96 4.) SERVICE DISCONNECT AT REAT OF STRUCTURE IN POOR AND DELAPIDATED SHAPE. UNSAFE CONDITIONS EXIST. PLEASE CORRECT. 5.) MAINTAIN WORKING CLEARENCES FOR SERVICE CONDUCTORS TO GROUND 230-24