Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/02/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) USE APPROVED FITTING AT LB-CHASE NIPPLE NOT APPROVED. 2.) IDENTIFYNEUTRAL CONDUCTOR CLOSER TO WATHER HEAD. 3.) NEED BONDING DEVICE ON OFFSET NIPPLE IN SERVICE GUTTER 250.94 4.) BOND GUTTER ENCLOUSER 250-96. |