Permit: T01EL02411

Parcel: 120071980

Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
09/27/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*1.) NEED TO HAVE ADDRESS POSTED ON BUILDING WHERE VISIBLE FROM STREET 2.) NEED SMOKE DETECTORS INSTALLED 3.) GROUNDED RECEPTACLES INSTALLED ON ONGROUNDED SYSTEM 4.) OPEN JUNCTION BOX ABOVE CLOSET 5.) PROPANE TANK OPERATING GAS STOVE 6.) UNSAFE CORDS USED AS WIRING METHOD 7.) EXPOSE WIRING TO ENTRY LIGHT AND IN KITCHEN CLOSET 8.) SECURE ALL CONDUITS ABOVE SERVICE AS PER CODE. 9.) METERS INCORRECTLY MARKED OR MISSING CNA NOT LOCATE METER FOR THIS SPACE. 10.) MISSING BREAKER WEATHER PROOF COVERS, 11.) NEED LICENSED ELECTRICAL CONTRACTOR TO PERFORM WORK 12.) WALL NOT ATTACHED KITCHEN CLOSET.