Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/23/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*APPROVED OK TO CLEAR SERVICE UP GRADE |
| 10/18/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) CANNOT ACCESS PANEL AT THIS TIME DUE TO BOXES IN FRONT OF SERVICE 2.) BOTTOM CONDUIT SUPPORT NOT ANCHORED TO WALL 3.) NEED 2 SUPPORTS ON RISER USE 1/4" MINIUM HARDWARE 4.)VERIFY GAS (BOTH METERS ) AND WATERBONDS. |