Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/07/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR. |
| 10/03/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1.) STRAP GROUNDWIRE AT FRONT PORCH 2.) MISSING JUNCTION BOX COVER 3.) JUNCTION BOX TO B ACCESSABLE 4.) LOOSE FITTING 5.) USE APPROVED FITTINGS TO L.B. CHASE NIPPLE NOT APPROVED. 6.) USE APPROVED SIZE CONDUCTORS FOR AMPACITY RATINGS 7.) DERATE CONDUCTORS AS PER CODE 310-15. |
| 09/30/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1.) VERIFY 2ND GROUND ROD -COULD NOT LOCATE. 2.) STRAP GROUND WIRE TO STRUCTURE OR BURY ENTIRE LENGTH OF RUNS.3.) INSTALL COVER MOUNTING HARDWARE CORRECTLY 4.) USE APPROVED FITTINGS TO LB-CHASE NIPPLE NOT APPROVED 5.) BOND JUNCTION BOX ENCLOUSER 6.) EXPOSE ROMEX BELOW 8' 7.) DERATE CONDUCTORS.8.) BOND WATER ON INTERIOR SIDE OF PIPEING 9.) NEED GUY BACK SUPPORT. |