Permit: T01EL02351

Parcel: 128010090


Addresses:

215 S CRAYCROFT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01EL02351

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/04/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000$
04/03/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*PLEASE HAVE ENGINEER OF RECORD SUBMIT A REVISED PANEL SCHEDULE FOR PANEL #DPH. ALL INFO SHOULD BE CONSISTENT WITH THE CIRCUIT BREAKER SIZE, WIRE SIZE, AND CONDUIT INSTALLED. THE REVISED PANEL SCHEDULE MUST BE SUBMITTED TO CITY OF TUCSON PLAN REVIEWER FOR APPROVAL STAMP AND SUBMITTAL OF COPY TO THE PUBLIC RECORD. THANKS.
01/25/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*CIRCUIT FOR PANELS P1-P2 &SCHOOL OFFICE HAS 2 3/0'S CU &1 #1L4 ON 200A 3 BREAKER EITHER PUT ON 150 A CB OR IF NOT REQUIRED REMOVE & PLACE ON 1 CB. PLAN DIFFERS FROM ON SITE CONDITIONS.