Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL02351
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000$ | |
04/03/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*PLEASE HAVE ENGINEER OF RECORD SUBMIT A REVISED PANEL SCHEDULE FOR PANEL #DPH. ALL INFO SHOULD BE CONSISTENT WITH THE CIRCUIT BREAKER SIZE, WIRE SIZE, AND CONDUIT INSTALLED. THE REVISED PANEL SCHEDULE MUST BE SUBMITTED TO CITY OF TUCSON PLAN REVIEWER FOR APPROVAL STAMP AND SUBMITTAL OF COPY TO THE PUBLIC RECORD. THANKS. | |
01/25/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*CIRCUIT FOR PANELS P1-P2 &SCHOOL OFFICE HAS 2 3/0'S CU &1 #1L4 ON 200A 3 BREAKER EITHER PUT ON 150 A CB OR IF NOT REQUIRED REMOVE & PLACE ON 1 CB. PLAN DIFFERS FROM ON SITE CONDITIONS. |