Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/30/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL. |
| 09/24/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) BOND ENCLOUSER EQUIPMENT DISCONNECT 2.) LABEL EQUIPMENT DISCONNECT. 3.) NEED TO SEE EQUIPMENT CONNECTIONS 4.) NEED TO SEE CONNECTIONS AT TERM CAN AFTER CROSSOVER 5.) FINISH BONDING OF TRANSFORMER AS PER CODE. OK TO CLEAR POWER. |
| 09/20/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) THIS IS NOT A SERVICE UPGRADE. THIS IS A NEW SERVICE WILL NEED PREMIT CHANGED. ALSO NEED A SET OF PLANS SHOWING EQUPTMENT LOCATION AND LOADS, TYPE OF EQUIPMENT PANEL TRANSFORMERS AND ALL ASSOCIATED ELECTRIC. MAY NEED A PLUMBING PERMIT ALSO FOR INSTULATION OF WATER LINES. 2.) PROVIDE FAULT CURRENT RATINGS SO AS TO DETRERMINE FUSING 3.) NEED REJECTION CLIPS AT SERVICE DISCONNECT 4.) WILL NEED TO SEE TERM CAN AFTER CONNECTIONS. |