Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/29/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) CANNOT USE CORD AS PERMANENT WIRING METHOD 400-8,400-7 2.) BROKEN FITTING AT SMALL MOTOR 3.) WORKING CLEARANCE CORRAOUSEL DISCONNECT 4.) DROP NOT SHOWN ON PLAN PLEASE REVISE FOR LOADS. |