Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/02/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 09/21/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000*NOTES OK CABLE DROP UNDERGROUND OK TO CLEAR METER. 1.) INSTALL CLOSE NIPPLE WITH LOCKNUT ON BOTH SIDES OF THE ENCLOSURE AND BONDING TYPE BUSHING DUE TO USE OF CONCENTRIC KNOCKOUTS USED. AT 1 1/2" CONDUIT TERMINATION AT PANEL. 1 1/2" ROMEX OR CABLE CONNECTOR NOT APPROVED TO TERMINATE 1 1/2" LB INTO PANEL. 2.) CALL FOR FINAL INSPECTION AFTER TIE-IN OF NEW SERVICE. |
| 09/19/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |