Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 10/09/2001 |
ELECTRIC - RECONNECT |
|
Denied |
MUST OBTAIN GENERAL REPAIR PERMIT AND RECALL INSPECTION. |
| 10/09/2001 |
ELECTRIC - RECONNECT |
|
Not ready for Inspection |
MUST OBTAIN GENERAL REPAIR PERMIT AND RECALL INSPECTION. |
| 10/05/2001 |
ELECTRIC - RECONNECT |
|
Denied |
CALLED OWNER MR ALEJANDRO GANEZ. LEFT MESSAGE MUST COMPLETE ALL REQUIRED BY CITY INSPECTOR BY TUESDAY OCT 9, 2001 OR RISK AN ORDER TO VACATE THE PREMISER, SEE WRITE UP OF 9/17/01 |
| 09/17/2001 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999*1.) FUSES MUST BE SIZED AS NOT TO EXCEDE NEC ART. 240. CHECK ALL FUSES. 2.) WILL NEED A SMOKE DETECTOR IN EACH BEDROOM. INSTALL PER MANUFACTURES INSTRUCTIONS 3.) WILL NEED TO REPAIR/CORRECT THE WROUGHT IRON BAR. THE WROUGHT IRON BAR CANNOT HAVE LOCKER, SPECIAL KNOWLEDGE OR EFFORT TO OPEN. 4.) SERVICE HAS A SUB PANEL ADDED TO THEIR. IMPROPER WIRING METHODS 5.) FASTEN GROUND WIRE TO WALL AND INSTALL A GROUNDING ELECTRODE SYSTEM. 6.) ALL OUTLET IN DINING ROOM ARE SWITCHED AND DINING LITE ENOPERABLE 7.) EXHAUST FAN 8.) DINING DOOR NOT WORKING NEED A LICENSED ELETRICAL CONTRACTOR TO MAKE REPAIR. |