Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T01EL02303
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/19/2001 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000* | |
09/13/2001 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999*1.) NEED PERMANENT METAL ADDRESS LABEL. 2.) BOND TO GAS PIPING 3.) USE APPROVED FITTING AND BONDING METHOD AT L.B. 4.) USE PROPER SPLICE METHODS FOR CONNECTING CONDOCTORS NEUTRAL. 5.) ROMEX IN NOT APPROVED FOR USE IN A RACEWAY SYSTEM 6.) USE ANTIOXIDE COMPOUND WITH ALUMINUM CONDUCTORS 7.) USE BREAKERS APPROVED FOR USE BY MANUFACTURE. 8.) RE-TIGHTEN MAIN NEUTRAL CONNECTION 9.) PLEAS VERIFY LICENSED ELECTRICAL CONTRACTOR. |