Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/25/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/03/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0215*THE FOLLOWING PROBLEMS MUST BE CORRECTED 1.) THE ELECTRICAL LOAD CENTER PANEL IS AN ARROW (AHM) HART MURRAY PRODUCT. THE MAIN CIRCUIT BREAKER HAS NO MARKINGS TO INDICATE IF IT IS AN AHM PRODUCT. 2.) THE MAIN CIRCUIT BREAKER APPREARS TO BE OF A LARGER AMPACITY THAN 100 AMPS. THE AMPERE RATING HAS BEEN REMOVED. 3.) SEVERAL NON AHM CIRCUIT BREAKERS HAVE BEEN FORCED INTO THE PANEL.4.) THE LINE WIRE FROM METER TO PANEL IS 210. MUCH LARGER THAN REQUIRED. 5.) THE METER CAN IS TOO SMALL FOR THE LINE & LOAD WIRES. |
| 09/28/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 09/27/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |