Permit: T01EL02281

Parcel: 134111220


Addresses:

8033 E 18TH PL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/25/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/03/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0215*THE FOLLOWING PROBLEMS MUST BE CORRECTED 1.) THE ELECTRICAL LOAD CENTER PANEL IS AN ARROW (AHM) HART MURRAY PRODUCT. THE MAIN CIRCUIT BREAKER HAS NO MARKINGS TO INDICATE IF IT IS AN AHM PRODUCT. 2.) THE MAIN CIRCUIT BREAKER APPREARS TO BE OF A LARGER AMPACITY THAN 100 AMPS. THE AMPERE RATING HAS BEEN REMOVED. 3.) SEVERAL NON AHM CIRCUIT BREAKERS HAVE BEEN FORCED INTO THE PANEL.4.) THE LINE WIRE FROM METER TO PANEL IS 210. MUCH LARGER THAN REQUIRED. 5.) THE METER CAN IS TOO SMALL FOR THE LINE & LOAD WIRES.
09/28/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
09/27/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*