Permit: T01EL02256

Parcel: 110080460

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/06/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP FRONT AND REAR UNITS.
09/07/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) 2 GOUND RODS REQUIRED, 2.) BOND NEUTRAL IN SUB PANEL REAR DWELLING. 3.) PHASE CONDUCTORS PROPER COLOR. 4.) EMT CONDUIT STUBBED INTO EARTH NEED ADDITIONAL CORROSION PROTECTION AND BUSHED END WHERE FEEDERS ENTER 45 BEND. 5.) BOND WATER & GAS PIPING.