Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL02254
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK TO CLEAR CALLED JUDY 8:23 AM FOR CLEARENCE LEFT MESSAGE ON MACHINE. | |
| 09/10/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) NEED BOND DEVICE BOTH SIDES OF NIPPLE AT SERVICE. 2.) CANNOT CUT DOWN CONDOCTORS TO FIT. 3.) BOND SUPPLY SIDE AS PER CODE 250-10L. 4.) PLEASE PROVIDE A FAULT CURRENT LETTER FROM TEP TO VERIFY FUSES. |