Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 12/26/2001 |
ELECTRIC - CABLE DROP |
|
Approved |
|
| 11/15/2001 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999*ARIZONA LAW REQUIRES THAT NAY ELECTRICAL WORK DONE ON YOUR R-2 GROUP HOME PROPERLY MUST BE DONE BY A LICENSED ELECTRICAL L-11 CLASS COTNRACTOR YOU MUST FURNISH THIS DEPARTMENT YOUR CONTRACTORS NAME, ADDRESS, PHONE NUMBER, AND CONTRACTORS LICENSE NUMBER BEFORE ANY INSPECTION WILL BE DONE. YOUR CONTRACTOR MAY CONTACTE ME AT 791-5550 EXT 136. THAN YOU MAC. |
| 10/11/2001 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0930* |
| 09/10/2001 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) INSTALL BOND BUSHINGS WHERE CONCENTRIC KO'S ARE USED. 2.) CHASE NIPPLES NOT ALLOWED. 3.) INSTALL PERMANENT ADDRESS LABEL ON SERVICE SCREWED OR RIVITED. 4.) SUPPORT 3/4" SEALITITE UP TO ROOF. 5.) I.D. CIRCUIT. BREAKERS 6.) 2 GROUND REQUIRED 6" APART MIN. 7.) BOND GAS LINE. |