Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T01EL02238
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2001 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection 0000*OK TO CLEAR. | |
| 09/07/2001 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*1.) BLOCK AND WHITE #10'S IN PANEL ARE TO BE ON A DOUBLE POLE 30 AMP CIRCUIT BREAKER. 2.) SEAL HOLE AT BOTTOM OF PANEL 3.) USE CIRCUIT BREAKER COVERS WHERE CIRCUIT BREAKERS MISSING IN PANEL 4.) OUTSIDE PANEL, THERE IS LIGHT ABOVE WHICH NEEDS TO HAVE A JUNCTION BOX BEHIND IT. 5.) LIGHT IN STORAGE ROOM INCORRECTLY INSTALLED, NEEDS TO HAVE A FIXTURE WHICH CONNECTS TO BOX 6.) INSTALL ALL FACE PLATES AND PROPERLY INSTALL RECEPTACLE AND SWITCH IN KITCHEN 7.) SOUTH LIVING ROOM WALL INSTALL ON EXTENTION RING AND BRING OUT RECEPTACLES TO DRY WALL SURFACE. | |
| 09/05/2001 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0210*THE ELECTRICAL PANEL & METER BASE ARE LOOSE. PLEASE SECURE THESE TO THE WALL WITH WOOD SCREWS. RECALL INSPECTION WHEN CORRECTED. |