Permit: T01EL02238

Parcel: 136214680

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T01EL02238

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2001 ELECTRIC - RECONNECT Approved IVRS - Inspection 0000*OK TO CLEAR.
09/07/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*1.) BLOCK AND WHITE #10'S IN PANEL ARE TO BE ON A DOUBLE POLE 30 AMP CIRCUIT BREAKER. 2.) SEAL HOLE AT BOTTOM OF PANEL 3.) USE CIRCUIT BREAKER COVERS WHERE CIRCUIT BREAKERS MISSING IN PANEL 4.) OUTSIDE PANEL, THERE IS LIGHT ABOVE WHICH NEEDS TO HAVE A JUNCTION BOX BEHIND IT. 5.) LIGHT IN STORAGE ROOM INCORRECTLY INSTALLED, NEEDS TO HAVE A FIXTURE WHICH CONNECTS TO BOX 6.) INSTALL ALL FACE PLATES AND PROPERLY INSTALL RECEPTACLE AND SWITCH IN KITCHEN 7.) SOUTH LIVING ROOM WALL INSTALL ON EXTENTION RING AND BRING OUT RECEPTACLES TO DRY WALL SURFACE.
09/05/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0210*THE ELECTRICAL PANEL & METER BASE ARE LOOSE. PLEASE SECURE THESE TO THE WALL WITH WOOD SCREWS. RECALL INSPECTION WHEN CORRECTED.