Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/12/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR 4202 E LOS ROBLES ST #2. |
| 09/11/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) CONTR. TO BE ON SITE NEXT INSPECTION TO REMOVE 6' GUTTER COVER FOR INSPECTION. 2.) INSTALL BOND BUSHINGS ON 1" CONDUIT CONNECTOR PER 250-94 NEC. 3.) COULD NOT REMOVE SMALL GUTTER COVER DUE TO SPLICES OR CONDUCTORS BINDING ON COVER. BRACE BACK CONDUCTORS. |
| 08/29/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES: THE N.E.C. 99" ALLOWS ONLY SIX DISCONNECTS MAX IN ONE LOCATION SERVED BY ONE SERVICE DROP 230-71 NEC 230-72. |