Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL02204
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/12/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK TO CLEAR 4202 E LOS ROBLES ST #2. | |
09/11/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTES 1.) CONTR. TO BE ON SITE NEXT INSPECTION TO REMOVE 6' GUTTER COVER FOR INSPECTION. 2.) INSTALL BOND BUSHINGS ON 1" CONDUIT CONNECTOR PER 250-94 NEC. 3.) COULD NOT REMOVE SMALL GUTTER COVER DUE TO SPLICES OR CONDUCTORS BINDING ON COVER. BRACE BACK CONDUCTORS. | |
08/29/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTES: THE N.E.C. 99" ALLOWS ONLY SIX DISCONNECTS MAX IN ONE LOCATION SERVED BY ONE SERVICE DROP 230-71 NEC 230-72. |