Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL02181
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK TO CLEAR. | |
09/05/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) NEED PERMANENT METAL ADDRESS LABEL. 2.) INSTALL GROUNDING ELECTRODE AND BONDING CONDUCTORS CORRECTLY. 3.) BOND GAS ON INTERIOR SIDE OF UNION 4.) NON WEATHER POROF FITTING USED OUTDOORS 5.) LB IN ACCESSABLE. 6.) USE 1/4" MININUM HARDWARE FOR 7.) USE CORRECT SIZED CONDUCTORS TO MATCH OVER CORRECT PROTECTION. 8.) MAIN BONDING JUMPER NEED 9.) CORRECTLY LABEL BREAKERS 10.) HAVE LICENSED ELECTRICAL CONTRACT ME BEFORE NEXT INSPECTION. | |
08/30/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0220*IN ORDER FOR YOUR GROUNDING SYSTEM TO BE MOST EFFECTIVE IT MUST BE INSTALLED PANEL GROUND BUSS TO COLD WTR. TO 1ST GRD ROD TO 2ND GRD. ROD THEN WTR PIPE TO GAS PIPE. TO AVOID FERRO MAGNETIC INDUCTION DO NOT COIL GROUND WIRE AROUND THE PIPES. USE THE PROPER STRAS TO ATTACH TO BUILDING (BRICK) SURFACE. THANKS CORRECT RECALL. |