Permit: T01EL02176

Parcel: 125042780


Addresses:

1916 E 2ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/23/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR FINAL.
01/15/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) CHASE NIPPLES ARE NOT APPROVED FITTINGS FOR USE WITH A L.B. PLEASE USE APPROVED FITTINGS. 2.) ENTRANCES TO PANEL ABOVE/SIDE OF THE BUSS REQUIRE A SEALING DEVICE. 3.) BREAKER ARE TO BE LISTED FOR USE BY THE MANFACTURE OF THE PANEL. 4.) PLEASE SUPPORT 1 1/4" CONDUIT WITHIN 3' OF L.B. 5.) INSULATION AROUND SPLIT BOLT TO BE EQEAL TO CONDUCTOR INSULATION USE APPROVED SPLICEING METHODS. 6.) FILL UNUSED OPENING AT SUB PANEL "B".