Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/23/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR FINAL. |
| 01/15/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) CHASE NIPPLES ARE NOT APPROVED FITTINGS FOR USE WITH A L.B. PLEASE USE APPROVED FITTINGS. 2.) ENTRANCES TO PANEL ABOVE/SIDE OF THE BUSS REQUIRE A SEALING DEVICE. 3.) BREAKER ARE TO BE LISTED FOR USE BY THE MANFACTURE OF THE PANEL. 4.) PLEASE SUPPORT 1 1/4" CONDUIT WITHIN 3' OF L.B. 5.) INSULATION AROUND SPLIT BOLT TO BE EQEAL TO CONDUCTOR INSULATION USE APPROVED SPLICEING METHODS. 6.) FILL UNUSED OPENING AT SUB PANEL "B". |