Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/31/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*OK CABLE DROP OK TO CLEAR. |
| 08/28/2001 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*1.) CANNOT LOCATE GROUND RODS. 2.) INSTALL PERMANENT ADDRESS LABEL. 3.) USE 1/4" BOLTS FOR RISER SUPPORT NOT #10 SMS. 4.) BOND WATER & GAS PIPING. 250-104 N.E.C. |