Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/20/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/10/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935*1.) CONDUIT NOT TO HAVE MORE THAN 360 IN ONE RUN WE HAVE 570 2.) 1 CIRCUIT SUPPLYING BUILDING, 1-CIRCUIT SUPPYING FAN/LITE A/C, LIGHTS, RECEPTACLES, REFRIDGIRATOR, & SMALL APPLAINANCE ON THIS ONE CIRCUIT NEED CIRCUITS TO HANDLE LOADS. 3.) FINISH CIRCLED ITEMS 4.) A REFEE HAS BEEN ASSESSED. |
| 09/26/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) FILL UNUSED OPENING IN PANEL 2.) INSTALL CONDUIT IN A WORKMAN LIKE MANNER 110-12. 3.) LOOSE CONDUIT FITTINGS. 4.) SUPPORT CONDUIT AS PER CODE. 5.) INSTALL ALL CIRCUITS TO BE USED WHERE IS POWER FOR HEATING AND COOLING. 6.) BOND ENCLOUSER. |
| 09/04/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0935* |
| 08/27/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 08/26/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.)FILL ALL UNUSED OPENING IN JUNCTION BOX 2.) LOOSE FITTING 3.) TRIPLE LUGING AT METER. 4.) GROUNDING ELECTRODE CONDUCTOR TO BE BONDED TO GROUNDED CONDUCTOR 5.) BOND AROUND GAS VALVES AND UNIONS 6.) GUY BACK BRACE TO BE SECURED TO RISER 7.) CONNECT ALL CIRCUITS. |