Permit: T01EL02149

Parcel: 10706032A


Addresses:

1261 W MIRACLE MILE

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/20/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/10/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0935*1.) CONDUIT NOT TO HAVE MORE THAN 360 IN ONE RUN WE HAVE 570 2.) 1 CIRCUIT SUPPLYING BUILDING, 1-CIRCUIT SUPPYING FAN/LITE A/C, LIGHTS, RECEPTACLES, REFRIDGIRATOR, & SMALL APPLAINANCE ON THIS ONE CIRCUIT NEED CIRCUITS TO HANDLE LOADS. 3.) FINISH CIRCLED ITEMS 4.) A REFEE HAS BEEN ASSESSED.
09/26/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) FILL UNUSED OPENING IN PANEL 2.) INSTALL CONDUIT IN A WORKMAN LIKE MANNER 110-12. 3.) LOOSE CONDUIT FITTINGS. 4.) SUPPORT CONDUIT AS PER CODE. 5.) INSTALL ALL CIRCUITS TO BE USED WHERE IS POWER FOR HEATING AND COOLING. 6.) BOND ENCLOUSER.
09/04/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0935*
08/27/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
08/26/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.)FILL ALL UNUSED OPENING IN JUNCTION BOX 2.) LOOSE FITTING 3.) TRIPLE LUGING AT METER. 4.) GROUNDING ELECTRODE CONDUCTOR TO BE BONDED TO GROUNDED CONDUCTOR 5.) BOND AROUND GAS VALVES AND UNIONS 6.) GUY BACK BRACE TO BE SECURED TO RISER 7.) CONNECT ALL CIRCUITS.