Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL02123
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 08/21/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0215*THE NEC ARE 230-40 DOES NOT PERMIT TWO SETS OF SERVICE ENTRANCE CONDUCTORS BE INSTALLED IN A SINGLE CONDUIT. THIS CAN BE DONE ONLY IF THE SERVICES ARE TAPPED TO/FROM A SINGLE SET OF CONDUCTORS. SIZED TO THE LOAD. THE ONLY WAY TWO SEPARATE SERVICE METER MAIN LOAD CENTER PANELS CAN BE CONNECTED TO THE SAME SERVICE LATERAL IS TO RAISE A SEPARATE MUST FROM EACH PANEL AND ALLOW THE POWER CO. TEP TO GROUP CONNECT AT THE WEATHER HEAD. |