Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01EL02115
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/30/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK TO CLEAR I-1,I-2,I-3,I-4 AND OWNERS METER. | |
08/27/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTES: 1. INSTALL BONDING TYPE BUSHING ON RISER CONDUIT & JUMPER TO ENCLOSURE. 250-94 N.E.C. 2. KO SEALS NOT RAINTITE. 3. REMOVE BOND SCREW ON NEUTRAL BUSS. 4. VIOLATION OF DEDICATED WORKING SPACE, REMOVE SHRUB OR RELOCATE NEW SERVICE TO COMPLY WITH110-26 N.E.C. |