Permit: T01EL02113

Parcel: 11202033A


Addresses:

2000 E ROGER RD A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/30/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR I-33, I-34 AND OWNERS METER.
08/27/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES: 1. REMOVE BOND SCREW ON NEUTRAL BUSS. 2. INSTALL BOND BUSHING ON RISER CONDUIT PER 250-94 N.E.C.
08/15/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*INSTALL GROUND BAR IN SUB-PANEL.