Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 09/05/2001 |
ELECTRIC - RECONNECT |
|
Approved |
IVRS - Inspection 0000* |
| 08/24/2001 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999*1.) HAVE ALL PREVIOUS PAPERWORK AT HOUSE 2.)NEED GENERAL REPAIR PERMIT FOR SERVICE PANEL BOARD REPLACEMENT 3.) NEED A PERMANENT ADDRESS TAP PER CITY ANMEND. 4.) NO GROUNDING ELECTRODE SYSTEM AT ALL 5.) A GROUNDING BUSHING AND BOND. JUMPER REQUIRED AT OFFSET NIPPLE. 6.) USING A G.E. BACK FED MAIN BREAKER MUST BE OF A PANEL BOARD LISTED BRAND AND MUST HAVE A RETAINER CLIP 7.) NEED WATER AND GAS BOND. 8.) METER BASE IS SO CROOKED THAT THE METER COVER WILL NOT LOCK IN PROPERLY 9.) PROPERLY REPAIR FURNACE EXHAUST VENT. |
| 08/23/2001 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0920* |
| 08/20/2001 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999* |
| 08/14/2001 |
ELECTRIC - RECONNECT |
|
Not ready for Inspection |
IVRS - Inspection 0000* |