Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL02102

Parcel: 10612048B


Addresses:

1415 W KILBURN ST

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/15/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0210*CHECKED WITH OFFICE. HAVE NOT RECEIVED LETTER TO VERIFY LICENSED ELECTRICAL CONTRACTOR.
08/14/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1.) NEED PERMANENT METAL ADDRESS LABEL. 2.) LABEL BREAKERS 3.) NEED GAS BOND 4.) FINISH DRIVING GROUND ROD. 5.) VERFY LICENSED ELECTRICAL CONTRACTOR 6.) USE CORRECT BREAKERS FOR CONDUCTOR AMPACITY.