Permit: T01EL02074

Parcel: 11706012B


Addresses:

240 N 2ND AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/24/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/02/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) PLEASE CLEAN SURFACE UNDER BOND CLAMPS2.) USE APPROVED FITTING AT LB. CHASE NIPPLE NOT APPROVED 3.) GROUNDING ELECTRODE CONDUCTOR TO BE CONNECTED TO GROUNDED CONDUCTOR. 4.) BALANCE LOAD IN PANEL 5.) CONNECT ALL CIRCUITS 6.) NEED PERMANENT METAL ADDRESS LABEL 6.) JUNCTION BOX TO BE WEATHER PROOF 8.) BOND JUNCTION BOX ENCLOUSE 9.) IDENTIFY NEUTRAL CLOSER TO WEATHER HEAD.