Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/24/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/02/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) PLEASE CLEAN SURFACE UNDER BOND CLAMPS2.) USE APPROVED FITTING AT LB. CHASE NIPPLE NOT APPROVED 3.) GROUNDING ELECTRODE CONDUCTOR TO BE CONNECTED TO GROUNDED CONDUCTOR. 4.) BALANCE LOAD IN PANEL 5.) CONNECT ALL CIRCUITS 6.) NEED PERMANENT METAL ADDRESS LABEL 6.) JUNCTION BOX TO BE WEATHER PROOF 8.) BOND JUNCTION BOX ENCLOUSE 9.) IDENTIFY NEUTRAL CLOSER TO WEATHER HEAD. |