Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL02067

Parcel: 11201020A


Addresses:

3922 N TUCSON BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/10/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
08/22/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES: 1.) EXPOSE BOTH GROUND RODS FOR INSPECTION. 2.) INSTALL BOND BUSHING ON 1/2" CONNECTOR KO. IS PULLING OUT. 250-94 N.E.C. 3.) INSTALL CONNECTOR WITH BUSHING ON END OF CONDUIT SLEEVE. 300-14 C N.E.C.
08/15/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*DID NOT WANT TO OPEN GATE TO DOG AREA PLEASE RECALL FOR INSPECTION WHEN SOMEONE WILL BE HERE & LEAVE A MESSAGE