Permit: T01EL02058

Parcel: 122173210

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/12/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR METER FOR GUEST HOUSE.
09/11/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) INSTALL BOND JUMPERS ON ENCLOSURES TO BOND BUSHING AT SERVICE. 2.) INSTALL BOND BUSHING ON FEEDER CONDUIT CONENCTOR AT GUEST HOUSE SUB PANEL. 3.) ISOLATE NEUTRAL GROUND BAR FROM EQUIP. GROUND BAR SEPARATE NEUTRALS AND GROUNDS. 4.) GROUNDING ELECTORDE SYSTEM AT GUEST HOUSE NOT TERMINATED IN PANEL. 5.) 70 AMP ITE MAIN BREAKER MUST BE RATED FOR REVERSE FEED AT GUEST HOUSE.
08/07/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) INSTALL FUSED COOLER BOX IN PLACE OF INDOOR RATED BOX AND RECEPT FOR COOLER.
08/07/2001 ELECTRIC - FINAL Denied 1.) INSTALL FUSED COOLER BOX IN PLACE OF INDOOR RATED BOX AND RECEPT FOR COOLER 2.) NEED ACCESS TO INSIDE OF UNIT.