Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T01EL02050

Parcel: 10714183A

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/07/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1.) NEED PERMANENT METAL ADDRESS LABEL 2.) PANEL COVER TO OPEN 90 3.) USE MANUFACTURES APPROVED HUB 4.) NEED TO SEE BONDING DEVICES IN METER AND PANEL 5.) SECURE CONDUITS AS PER CODE. 6.) LOOSE FITTINGS 7.) NEED 1/4" MINIMUN HARDWARE TO SUPPR RISER 8.) NEED GROUNDING ELECTRODE SYSTEM 9.) PROVIDE FOR CORRECT CLEARANCE OVER DRIVE WAY.